Calcium Sulphate Access Floor System

Description




Calcium Sulphate Access Floor System



The Calcium Sulphate Access Floor

ATFLOR Calcium Sulphate Access Floor panels consist of environment friendly calcium sulphate board glue to and galvanized steel sheet on bottom. These panels have a class A flame spread rating and provide excellent rigidity, durability, and acoustic performance. Calcium Sulphate Access Floor panels are engineered to meet Tate Standards per CE& CISCA testing methods.


Key Performance Characteristics

· Panel weight : 18 kg/pc, bare.

· panel- calcium sulphate board ,PVC/ABS corvered four edges,steel on the bottom plate.

· Accessories -die casting steel structure pedestal plastic gasket on top ,height could be 70mm ---1500mm , with or without square tube stringer steady connect the system

· ULC File Number: R16784.


System Performance

ATFLOR Standards to CE& CISCA Testing Methods


Technical Data

International

Concentrated Load

Impact Load (N)

Ultimate Load (N)

Uniform Load (N/M2)

Rolling Load(N)

LB

N

KG

10 Times

10000 Times

FS800

≥800

≥3350

≥363

≥536

≥11250

≥16100

3560

2670

FS1000

≥1000

≥4550

≥450

≥670

≥13350

≥23000

4450

3560

FS1250

≥1250

≥5560

≥567

≥780

≥16680

≥33000

5560

4450

FS1500

≥1500

≥6675

≥670

≥1005

≥19892

≥34500

6675

5340

*All tests are performed using CE& CISCA's Recommended Test Procedures for Access Floors


Laminates for Data Centers

Laminates for Data Centers

High pressure laminates (HPL) and Vinyl are the mostly adopted finishes on an access floor in data centers.

  Key Performance Characteristics 

  · Superior wear resistance will not detach, chip or crack

  · Simple maintenance with mop cleaning

  · Visually appealing with a wide range of color options

 






ATFLOR offers a variety of laminates for use inside of data centers. High pressure laminates (HPL) and static control vinyl laminates are factory laminated to the access floor systems, reducing installation time and cost. HPL in data centers is the most common finish found on an access floor and complies with requirements for low static generation and retention and assures ease of maintenance.

Static control vinyl is specifically designed to control static discharge.  Which helps protect your most sensitive equipment and critical applications by keeping static away.

 

Laminate Finishes Proposal

Product

Manufacturer

Details

Style

HPL

Maite 

Laminated Floor Tile

Standard Dissipative HPL

HPL

Meiah

Laminated Floor Tile

High Pressure Laminate

Static Control Vinyl

HJ

Conductive&Static Dissipative

Conductive or Dissipative Vinyl

Static Control Vinyl

ATFLOR

Static Dissipative

Homogeneous PVC Tile


Understructure Options

The Heavy Duty Bolted Stringer Understructure System

ATFLOR Heavy Duty Bolted Stringer Understructure System is designed for computer rooms, data centers, industrial applications and heavy rolling load areas.

  Key Performance Characteristics 

  · Designed for computer rooms, data centers, industrial applications, and heavy rolling load areas

  · Allowing floors to be installed over 1500mm high

  · Gravity-held in understructure for fast removal and replacement

  · Stringers providing lateral resistance to heavy rolling loads

  · Available seismic resistant pedestal to limit or eliminate the requirement for special bracing